New Trend Electrical Appliance Group Co., Ltd.

 Products >>Motion Control >> HMI / PLC >>PLC - XCX5 SERIES (ECONOMICAL)

Item No : PLC - XCX5 SERIES (ENHANCED)
Name : PLC - XCX5 SERIES (ENHANCED)
Type : HMI / PLC
Description :
>>PLC CATALOG
XCX5-32R-E XCX5(enhanced)
  18 DI/14 DO, AC220 power supply
Owns the whole functions of XC3 series
Support 4 channels pulse output
 
General Specifications

Item
Specification
Insulation Voltage
Above DC 500V 2MΩ
Noise Resistance
1000V 1uS pulse for 1 minute
Environment Temperature
0℃~60℃
Ambient Humidity
5%~95%
COM 1
RS-232, be connected to host machine or HMI for programming or debugging
COM 2
RS-485/RS-232,network or connect to intelligent instrument, inverter, etc.
COM 3
Communication port RS-485/RS232 on BD board
Installation
M3 screw fixed or DIN46277 (35mm width) guide rail  installation
Grounding
The third type grounding (Never perform common grounding with strong power system)

Functional Specifications

Item
Specification
Program Operation Mode
Circulation scanning mode, timing scanning mode
Program Mode
Instructions and ladder chart
Dispose Speed
0.5us
Power Failure Holding
FlashROM
User Program’s Capacity
8000 steps
I/O Points
18 input points,14 output points
Output Format
Relay
Power Supply
AC220V
Interior Coil’s Points (M)
8512 points
 
Timer(T)
Points
620 points
Specification
100mS timer:set time 0.1~3276.7 seconds
10mS timer:set time 0.01~327.67 seconds
1mS timer:set time 0.001~32.767 seconds
 
Counter(C)
Points
635 Points
Specification
16 bits counter::Set value K0~32767
32 bits counter:Set value K0~2147483647
Data Register(D)
8512 characters
FlashROM Register(FD)
6144 characters
High-speed Count Format
High speed counter, pulse output, exterior interruption
Timing Scanning Interval Setting
1~99mS
Password Protection
6 characters ASCII
Self-diagnose Function
Power on self-diagnose, monitor timer, grammar check

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
Note: “-s” added behind the model name means it with internal clock and RS-485 communication port.

XCX5-48R-E XCX5(enhanced)
  28 DI/20 DO, AC220 power supply
Owns the whole functions of XC3 series products
Support 4 channels pulse output
 
General Specifications

Item
Specification
Insulation Voltage
Above DC 500V 2MΩ
Noise Resistance
1000V 1uS pulse for 1 minute
Environment Temperature
0℃~60℃
Ambient Humidity
5%~95%
COM 1
RS-232, be connected to host machine or HMI for programming or debugging
COM 2
RS-485/RS-232,network or connect to intelligent instrument, inverter, etc.
COM 3
Communication port RS-485/RS232 on extensional BD board
COM 4
Communication port for CAN bus
Installation
M3 screw fixed or DIN46277 (35mm width) guide rail  installation
Grounding
The third type grounding (Never perform common grounding with strong power system)

 Functional Specifications

Item
Specification
Program Operation Mode
Circulation scanning mode, timing scanning mode
Program Mode
Instructions and ladder chart
Dispose Speed
0.5us
Power Failure Holding
FlashROM
User Program’s Capacity
8000 steps
I/O Points
28 input points,20 output points
Output Format
Relay
Power Supply
AC220V
Interior Coil’s Points (M)
8512 points
 
Timer(T)
Points
620 points
Specification
100mS timer:set time 0.1~3276.7 seconds
10mS timer:set time 0.01~327.67 seconds
1mS timer:set time 0.001~32.767 seconds
 
Counter(C)
Points
635 Points
Specification
16 bits counter::Set value K0~32767
32 bits counter:Set value K0~2147483647
Data Register(D)
8512 characters
FlashROM Register(FD)
6144 characters
High-speed Count Format
High speed counter, pulse output, exterior interruption
Timing Scanning Interval Setting
1~99mS
Password Protection
6 characters ASCII
Self-diagnose Function
Power on self-diagnose, monitor timer, grammar check

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Note:
“-s” added behind the model name means it with internal clock and RS-485 communication port.

XCX5-60R-E XCX5(enhanced)
  36 DI/24 DO, AC220 power supply
Owns the whole functions of XCX3 series products
Support CAN bus as well as CAN bus network
 
General Specifications

Item
Specification
Insulation Voltage
Above DC 500V 2MΩ
Noise Resistance
1000V 1uS pulse for 1 minute
Environment Temperature
0℃~60℃
Ambient Humidity
5%~95%
COM 1
RS-232, be connected to host machine or HMI for programming or debugging
COM 2
RS-485/RS-232,network or connect to intelligent instrument, inverter, etc.
COM 3
Communication port RS-485/RS232 on extensional BD board
COM 4
Communication port for CAN bus
Installation
M3 screw fixed or DIN46277 (35mm width) guide rail  installation
Grounding
The third type grounding (Never perform common grounding with strong power system)

Functional Specifications

Item
Specification
Program Operation Mode
Circulation scanning mode, timing scanning mode
Program Mode
Instructions and ladder chart
Dispose Speed
0.5us
Power Failure Holding
FlashROM
User Program’s Capacity
10000 steps
I/O Points
26 input points,24 output points
Output Format
Relay
Power Supply
AC220V
Interior Coil’s Points (M)
8512 points
 
Timer(T)
Points
620 points
Specification
100mS timer:set time 0.1~3276.7 seconds
10mS timer:set time 0.01~327.67 seconds
1mS timer:set time 0.001~32.767 seconds
 
Counter(C)
Points
635 Points
Specification
16 bits counter::Set value K0~32767
32 bits counter:Set value K0~2147483647
Data Register(D)
8512 characters
FlashROM Register(FD)
6144 characters
High-speed Count Format
High speed counter, pulse output, external  interruption
Timing Scanning Interval Setting
1~99mS
Password Protection
6 characters ASCII
Self-diagnose Function
Power on self-diagnose, monitor timer, grammar check

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Note:
“-s” added behind the model name means it with internal clock and RS-485 communication port.